  • 1-201230095328_副本.jpg
  • 1-201230095335_副本.png

Optical fiber composite overhead ground wire OPGW-layer stranded type

Optical fiber composite overhead ground wire OPGW-layer stranded type Product Description Optical Fiber Composite Overhead Ground Wire (OPGW) is an overhead ground wire containing optical fibers. It has multiple functions such as overhead ground wire and optical communication. It is mainly used for communication lines of 110KV, 220KV, 500KV, 750KV and new overhead high voltage transmission systems. can also be used for more...

Classification:


Keyword: Optical fiber composite overhead ground wire OPGW-layer stranded type

Product Consulting:

Product Description

Product Description

Optical fiber composite overhead ground wire (OPGW) is a kind of overhead ground wire containing optical fiber, which has multiple functions such as overhead ground wire and optical communication. It is mainly used for communication lines of 110KV, 220KV, 500KV, 750KV and new overhead high voltage transmission system. It can also be used to replace the existing ground wire of the old overhead high-voltage transmission system, increase optical communication lines, conduct short-circuit current and provide anti-lightning protection. Special structure can be customized according to user needs.

Product Features

· Large cable diameter, large number of fiber cores can be designed;

· Stable structure and high reliability;

· The tensile strength and short-circuit current capacity are large, which can achieve the best balance of mechanical and electrical properties;

· The best stranded design, can obtain the secondary fiber length;

· Strand layers can be designed with two or three layers;

• The monofilament may be an aluminum-clad steel wire and an aluminum alloy wire, an aluminum wire combination.

Product Standards

Meet DL/T832-2016 standard optical characteristics

  G652 G655 50/125 62.5/125
Attenuation 1310 nm ≤ 0.35 db/km      
1550 nm ≤ 0.21 db/km ≤ 0.22 db/km    
850 nm     ≤ 3.0 db/km ≤ 3.5 db/km
1300 nm     ≤ 1.0 db/km ≤ 1.0 db/km
Bandwidth (Class A) 850 nm     ≥ 600 MHz · km ≥ 200 MHz · km
1300 nm     ≥ 1200 MHz · km ≥ 600 MHz · km
numerical aperture     0.200±0.015NA 0.275±0.015NA
Cable end wavelength ≤ 1260 nm ≤ 1450 nm    

structural parameters

  Type Materials Numerical
Structure optical fiber G652D / G655 etc 2-144 core
Protective tube Stainless steel pipe 1.5-6.0mm
Stranked single wire aluminum clad steel/aluminum alloy/aluminum rod 1.5-6.0mm
Maximum outer diameter 30mm
Maximum cross-sectional area 500mm ²
Mechanical properties Maximum pull force (RTS)KN 700
Maximum crushing force (N/100mm) 3000
Maximum short-circuit current capacity (40 ℃ ~ 200 ℃)(kA2s) 2000
Minimum bending radius (dynamic) 20D
Minimum bending radius (static) 15D
Environmental Performance Installation temperature range (℃) -10~ 50
Operating and storage temperature range (℃) -40~ 65

Specific models and technical parameters

Serial Number Technical parameters
Product Model Optical cable structure form Maximum number of fibers
(core)
aluminum clad steel section
(mm2)
Outer diameter
(mm)
Mass per unit length
(kg/km)
Rated breaking force
(kN)
20 ℃ DC resistance
(Ω/km)
Allowable short-circuit current capacity
(40-200 ℃ kA2.s)
1 OPGW-48B1.3-90- [112;45] 1/2.6/20AS+4/2.5/20AS+
11/2.8/20AS, Light Unit 2/2.5
48 ≈ 90 13.2 ≤ 641 ≥ 112 ≤ 0.98 ≥45
 
2
OPGW-48B1.3-90- [57;67] 1/2.6/40AS+4/2.5/40AS+
11/2.8/40AS, Light Unit 2/2.5
48 ≈ 90 13.2 ≤ 457 ≥ 57 ≤ 0.52 ≥ 67
 
3
OPGW-24B1.3-100-[118;50] 1/2.6/20AS+5/2.5/20AS+
11/2.8/20AS, light unit 1/2.5
24 ≈ 100 13.2 ≤ 674 ≥ 118 ≤ 0.93 ≥50
 
4
OPGW-24B1.3-100-[60;74] 1/2.6/40AS+5/2.5/40AS+
11/2.8/40AS, light unit 1/2.5
24 ≈ 100 13.2 ≤ 479 ≥60 ≤ 0.49 ≥ 74
5 OPGW-24B1.3-110-[133;63] 1/2.6/20AS+5/2.5/20AS+
10/3.2/20AS, light unit 1/2.5
24 ≈ 110 14 ≤ 760 ≥ 133 ≤ 0.83 ≥ 63
 
6
OPGW-24B1.3-110-[140;68] 1/2.8/20AS+5/2.7/20AS+
11/3.05/20AS, light unit 1/2.6
24 ≈ 110 14.3 ≤ 791 ≥ 140 ≤ 0.80 ≥ 68
 
7
OPGW-24B1.3-110-[67;95] 1/2.9/20AS+5/2.8/20AS+
12/2.8/AA, light unit 1/2.7
24 ≈ 37
≈74(AA)
14.1 ≤ 473 ≥ 67 ≤ 0.40 ≥95
 
8
OPGW-36B1.3-120-[145;73] 1/3.0/20AS+5/2.9/20AS+
12/2.9/20AS, light unit 1/2.8
36 ≈ 120 14.6 ≤ 820 ≥ 145 ≤ 0.77 ≥ 73
 
9
OPGW-36B1.3-120-[95;98] 1/3.0/30AS+5/2.9/30AS+
12/2.9/30AS, light unit 1/2.8
36 ≈ 120 14.6 ≤ 700 ≥95 ≤ 0.55 ≥98
10 OPGW-36B1.3-120-[74;110] 1/3.0/40AS+5/2.9/40AS+
12/2.9/40AS, light unit 1/2.8
36 ≈ 120 14.6 ≤ 582 ≥ 74 ≤ 0.42 ≥ 110
 
11
OPGW-72B1.3-120-[147;76] 1/3.2/20AS+4/3.0/20AS+
12/3.0/20AS, Light Unit 2/2.9
72 ≈ 120 15.2 ≤ 832 ≥ 147 ≤ 0.76 ≥ 76
 
12
OPGW-72B1.3-120-2[96;101] 1/3.2/30AS+4/3.0/30AS+
12/3.0/30AS, light unit 2/2.9
72 ≈ 120 15.2 ≤ 711 ≥ 96 ≤ 0.53 ≥ 101
 
13
OPGW-72B1.3-120-[74;114] 1/3.2/40AS+4/3.0/40AS+
12/3.0/40AS, light unit 2/2.9
72 ≈ 120 15.2 ≤ 591 ≥ 74 ≤ 0.40 ≥ 114
4 OPGW-36B1.3-130-[155;85] 1/3.2/20AS+5/3.0/20AS+
12/3.0/20AS, light unit 1/2.9
36 ≈ 130 15.2 ≤ 879 ≥ 155 ≤0.72 ≥85
 
15
OPGW-36B1.3-130-[102;114] 1/3.2/30AS+5/3.0/30AS+
12/3.0/30AS, light unit 1/2.9
36 ≈ 130 15.2 ≤ 751 ≥ 102 ≤0.50 ≥ 114
 
16
OPGW-36B1.3-130-[79;137] 1/3.2/40AS+5/3.0/40AS+
12/3.0/40AS, light unit 1/2.9
36 ≈ 130 15.2 ≤ 624 ≥ 79 ≤ 0.40 ≥ 137
 
17
OPGW-36B1.3-140-[175;100] 1/3.3/20AS+5/3.2/20AS+
12/3.2/20AS, light unit 1/3.1
36 ≈ 140 16.1 ≤ 995 ≥ 175 ≤ 0.65 ≥ 100
 
18
OPGW-36B1.3-140-[115;140] 1/3.3/30AS+5/3.2/30AS+
12/3.2/30AS, light unit 1/3.1
36 ≈ 140 16.1 ≤ 850 ≥ 115 ≤ 0.45 ≥ 140
 
19
OPGW-36B1.3-145-[86;170] 1/3.3/20AS+5/3.2/20AS+
12/3.2/AA, light unit 1/3.1
36 ≈ 49
≈96(AA)
16.1 ≤ 611 ≥ 86 ≤ 0.31 ≥ 170
 
20
OPGW-48B1.3-150-[182;123] 1/3.4/20AS+5/3.3/20AS+
12/3.3/20AS, light unit 1/3.2
48 ≈ 150 16.6 ≤ 1055 ≥ 182 ≤ 0.60 ≥ 123
 
21
OPGW-48B1.3-150-[122;165] 1/3.4/30AS+5/3.3/30AS+
12/3.3/30AS, light unit 1/3.2
48 ≈ 150 16.6 ≤ 901 ≥ 122 ≤ 0.42 ≥ 165
 
22
OPGW-48B1.3-150-[95;195] 1/3.4/40AS+5/3.3/40AS+
12/3.3/40AS, light unit 1/3.2
48 ≈ 150 16.6 ≤ 747 ≥95 ≤ 0.33 ≥ 195
 
23
OPGW-72B1.3-150-[172;110] 1/3.4/20AS+4/3.3/20AS+
12/3.3/20AS, Light Unit 2/3.2
72 ≈ 150 16.6 ≤ 998 ≥ 172 ≤ 0.64 ≥ 110
 
24
OPGW-72B1.3-150-[116;147] 1/3.4/30AS+4/3.3/30AS+
12/3.3/30AS, light unit 2/3.2
72 ≈ 150 16.6 ≤ 853 ≥ 116 ≤ 0.45 ≥ 147
 
25
OPGW-48B1.3-170-[198;150] 1/3.6/20AS+5/3.5/20AS+
12/3.5/20AS, light unit 1/3.4
48 ≈ 170 17.6 ≤ 1190 ≥ 198 ≤ 0.54 ≥ 150
 
26
OPGW-72B1.3-170-[199;156] 1/3.8/20AS+4/3.6/20AS+
12/3.6/20AS, Light Unit 2/3.5
72 ≈ 170 18.2 ≤ 1187 ≥ 199 ≤ 0.54 ≥ 156
 
27
OPGW-48B1.3-180-[252;125] 1/3.8/14AS+5/3.6/14AS+
12/3.6/14AS, light unit 1/3.5
48 ≈180 18.2 ≤ 1372 ≥ 252 ≤0.72 ≥ 125
 
28
OPGW-48B1.3-180-[211;175] 1/3.8/20AS+5/3.6/20AS+
12/3.6/20AS, light unit 1/3.5
48 ≈180 18.2 ≤ 1255 ≥ 211 ≤0.50 ≥ 175
 
29
OPGW-48B1.3-180-[147;234] 1/3.8/30AS+5/3.6/30AS+
12/3.6/30AS, light unit 1/3.5
48 ≈180 18.2 ≤ 1071 ≥ 147 ≤ 0.35 ≥ 234
 
30
OPGW-48B1.3-180-[113,262] 1/3.8/40AS+5/3.6/40AS+
12/3.6/40AS, light unit 1/3.5
48 ≈180 18.2 ≤ 888 ≥ 113 ≤ 0.28 ≥ 262
 
31
 
OPGW-48B1.3-235-[268;243]
1/2.7/20AS+4/2.5/20AS+
12/2.5/20AS 13/3.8/20AS,
Light unit 1/3.5
 
48
 
≈ 235
 
20.3
 
≤ 1594
 
≥ 268
 
≤ 0.38
 
≥ 243

Mechanical and environmental performance testing

Project Test Method Acceptance Criteria
Pull force GB/T 7424.2-E1
Load: according to the change of optical cable structure, sample length: not less than 10m; Link not less than 100m Duration: 1min
The 40% RTS fiber has no significant strain (0.01%) and the fiber has no significant additional attenuation (0.03dB).
60% RTS fiber strain ≤ 0.25, fiber additional attenuation ≤ 0.05dB (after the tension is canceled, the fiber has no significant residual additional attenuation (0.03dB)).
Squash GB/T 7424.2-E3
Load: according to the above table, test 3 points duration: 10min
After the test, the additional attenuation of the single-mode fiber at the wavelength of 1550nm shall not be greater than 0.05dB/fiber, and the OPGW shall be free of mechanical damage.
water seepage GB/T 7424.2-F5
Time: 1 hour Sample length: 0.5m Water height: 1m
No water seepage.
Temperature cycle GB/T 7424.2-F1
Sample length: not less than 500m Temperature range:-40 ℃ ~ 70 ℃ Cycle times: 2 Holding time: not less than 12h
After the test, the additional attenuation of the single-mode fiber at the wavelength of 1550nm shall not be greater than 0.1dB.

Delivery length
The recommend length is 2000 meters/3000 meters, and other lengths can be provided according to customer requirements.

Product inquiry

We will contact you within one working day. Please pay attention to your email.

Submit
Business License